OVR Type 2 surge protective devices – TNS
Extended Product Type : OVR T2 4L 40-275 P QS
Product ID : 2CTB803873R5600
Standards : IEC 61643-11 / EN 61643-11
Product Main Type : T2
Nominal AC Voltage of the System (Uo) : 230 / 400 V
Maximum Continuous Operating Voltage (Uc) : 275 V
Nominal Discharge Current In(8/20µs) : 20 kA
Maximum Discharge Current Imax(8/20µs) : 40 kA
Maximum Impulse Current Iimp(10/350µs) : 2 kA
Voltage Protection Level (Up) at In : 1.25 kV
– Pluggable cartridge (P)
– Integrated QuickSafe technology (QS)