OVR Plus autoprotected surge protection devices
Extended Product Type : OVR PLUS N1 40
Product ID : 2CTB803701R0100
Standards : IEC 61643-1 / EN 61643-11
Product Main Type : T2
Nominal AC Voltage of the System (Uo) : 230 / 400 V
Maximum Continuous Operating Voltage (Uc) : 275 V
Nominal Discharge Current In(8/20µs) : 5 kA
Maximum Discharge Current Imax(8/20µs) : 20 kA
Voltage Protection Level (Up) at In (L-N / N-PE / L-PE) : 1.3 / – / 1.3 kV
TOV (Temporary overvoltage) withstand (L-N:5s./N-PE:200ms) : 334 / 1200 V
Response time : ≤ 25 ns
– Integrated QuickSafe technology (QS)
– State indicator